To Get any support : +88 02-8981255
4090-9116 Addressable IDNet Communications Isolators provide IDNet communications isolation to improve installation convenience and increase system integrity. Isolation is automatically activated when an output short circuit is detected and isolation can also be selected manually from the control panel to assist with troubleshooting wiring problems.
Operation. Isolators power-up in isolation mode and are directed to connect by the control panel. If the output wiring is acceptable, the isolator will connect to the rest of the circuit. If the output wiring is shorted, the isolator remains isolated.
Dual port, bi-directional communications short circuit isolator:
PRODUCT SELECTION
4090-9116 | Addressable IDNet Communications Isolator | |
4090-9813 | Adapter plate to fit 4 11⁄16” (119 mm) square electrical box | |
4090-9801 | For semi-flush mounted box | Optional trim plate with LED viewing window, includes mounting screws; galvanized steel |